Configured for signal interfacing and transducer power distribution in FieldMonitor instrumentation platforms, the Bently Nevada 170180-01-00 (170180 External Transducer I/O Module) provides direct physical/electrical execution.

Suffix Breakdown & Model Matrix

Option Field Code Configuration Detail
Core Assembly 170180 FieldMonitor External Transducer I/O Module base unit
Channel & Hardware Version 01 Standard 2-channel dynamic transducer interface configuration
Agency / Option Code 00 Standard uncertified configuration / baseline options

Hardware Specifications

Parameter Specification
Model 170180-01-00
Brand Bently Nevada
Origin USA
Weight 277 g (0.61 lbs)
Dimensions Standard FieldMonitor external I/O footprint
Operating Temp -34 deg C to +85 deg C (-30 deg F to +185 deg F)
Power Consumption Current draw: 2.0 mA maximum (without transducer load)
Number of Channels 2 independent channels
Input Signals Channel A & B: -24 VDC Proximitor Sensor or Accelerometer
Frequency Response -5% at greater than 25 kHz
Current Limit Setpoint 33.6 mA minimum to 37.6 mA maximum at +25 deg C (+77 deg F)

Eddy-Current Probe Scaling and Gap Voltage Validation

The 170180-01-00 conditions analog dynamic signals from eddy-current proximity probes and accelerometers across two distinct channels. Integrated signal path architecture provides precise eddy-current probe scaling for accurate shaft position and dynamic vibration feedback. During startup and routine diagnostics, DC gap voltage validation verifies proper transducer position within its linear range, ensuring that baseline bias voltage is maintained while executing high-frequency response up to 25 kHz with minimal harmonic distortion.

Frequently Asked Questions

Q: What input signals are supported by Channel A and Channel B on the 170180-01-00?

A: Both channels support -24 VDC Proximitor Sensor inputs or piezoelectric accelerometers configured for dynamic vibration and position measurements.

Q: How does the current limit setpoint protect the module from field wiring faults?

A: The internal current limiting circuitry bounds transducer loop supply current between 33.6 mA and 37.6 mA at +25 deg C (+77 deg F) to suppress damage caused by shorted signal leads or cable faults.

Field Installation Guidelines

  1. Ensure power to the target FieldMonitor system is turned off prior to mounting or wiring the I/O module.
  2. Secure the 170180-01-00 chassis to the designated mounting plate using appropriate hardware.
  3. Wire Channel A and Channel B -24 VDC Proximitor or accelerometer leads to the assigned screw terminal connections.
  4. Terminate signal cable drain wires at the local system ground bar using a single-point connection strategy to avoid ground loop noise coupling.
  5. Verify that operating temperatures remain within -34 deg C to +85 deg C during field service.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

System reliability directly determines operational profitability across high stakes process industries. Modern industrial automation platforms must eliminate single points of failure to prevent catastrophic shutdowns. Deploying fault tolerant architecture safeguards complex facilities against unexpected hardware glitches, network disruptions, and maintenance outages.

Read more
Understanding Types of Noise in Electronic Circuits and Control Systems

Understanding Types of Noise in Electronic Circuits and Control Systems

Signal integrity directly determines measurement accuracy and loop stability across industrial automation environments. Electronic noise introduces unwanted stochastic interference into analog loops, sensor feedback lines, and digital fieldbus networks. Understanding how intrinsic electronic noise and external electromagnetic interference manifest allows control engineers to optimize signal conditioning and shield sensitive instrumentation effectively.

Read more
Why 24V DC Power Supplies Standardize Modern Industrial Automation

Why 24V DC Power Supplies Standardize Modern Industrial Automation

Industrial control cabinets worldwide rely on 24V DC as the universal power standard for field instrumentation, sensors, and controllers. Walk into any manufacturing plant, and you will find PLCs, human-machine interfaces (HMIs), and smart actuators running on extra-low voltage DC. Standardizing on 24V DC enhances operational safety, lowers cabinet footprint, and maintains steady control performance across factory networks.

Read more