Product Details
The Honeywell 900C53-0001, also cataloged as the 900C53 Analog Output Module, operates as a dedicated hardware component for 4-channel analog signal execution within Honeywell HC900 Controller networks.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 900C53-0001 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.35 kg |
| Operating Temp | -40 deg C to 60 deg C |
| Power Consumption | Backplane powered via HC900 controller rack |
| Channel Count | 4 isolated output channels |
| Output Signal Type | 4-20 mA DC, 0-10 VDC |
| Resolution | 12-bit D/A conversion |
| Accuracy | +0.1 percent of full scale |
| Isolation | 1500 V RMS between field and logic |
| Response Time | Less than 2 ms |
| Storage Temp | -40 deg C to 85 deg C |
| Part Number Secondary | 51500189-0012 |
4-20 mA HART Loop & Channel-to-Channel Isolation
The 900C53-0001 module executes digital-to-analog conversion at 12-bit resolution to drive final control elements in process control loops. Field circuitry is isolated from backplane logic at up to 1500 V RMS, shielding internal controller buses from common-mode voltage spikes and electrical noise. Capable of sourcing both 4-20 mA current signals and 0-10 VDC outputs, the module integrates directly with standard 4-20 mA HART loop devices and field actuators requiring continuous analog control updates under 2 ms.
Frequently Asked Questions
Q: What is the galvanic isolation rating between field wiring terminals and the backplane logic on the 900C53-0001?
A: The module provides galvanic isolation rated at 1500 V RMS between field-side outputs and the internal system backplane logic.
Q: Can the output channels be configured independently for current and voltage modes?
A: Channel configurations allow signal output paths to be set for either 4-20 mA current loops or 0-10 VDC voltage control per application requirements.
Field Installation Guidelines
- Turn off backplane rack power prior to inserting or removing the module from the HC900 terminal rack base.
- Route current loop field conductors using shielded twisted-pair cables, bonding the overall shield to chassis ground at a single end.
- Confirm that field device load impedance complies with module drive specifications for 4-20 mA current loops and 0-10 VDC voltage circuits.
- Verify all terminal connection screws are secured tightly to prevent high-resistance field loop faults under continuous operational vibration.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.