Product Details

Configured for high-voltage signal attenuation and ground detection interfacing in EX2100 excitation systems, the General Electric IS200EXAMG1AAB (IS200EXAMG1AAB Exciter Attenuation Module) provides direct physical/electrical execution of field bus voltage reduction and signal feedback conditioning.

Hardware Specifications

Parameter Specification
Model IS200EXAMG1AAB
Brand General Electric
Origin United States (USA)
Operating Temp 0 deg C to 40 deg C
Channels 13
AC Input Frequency 480 Hz (max)
Field Voltage Range 125 V dc to 1000 V dc
PPT Voltage Range 120 V ac to 1300 V ac rms

Excitation Control and Feedback Response

The IS200EXAMG1AAB module is engineered to regulate field current and voltage feedback by attenuating high-voltage bridge signals to levels compatible with the Exciter Ground Detector Module (EGDM). The module supports deterministic network connectivity via the Exciter Power Backplane (EPBP), utilizing a 9-pin interface to ensure low-latency feedback transmission. Its internal architecture is compatible with both simplex and triple modular redundant (TMR) control sections, requiring only a single EXAM unit per system regardless of redundancy configuration. The module’s attenuation circuitry is field-selectable via jumper settings (JP1 and JP2) to accommodate specific power potential transformer (PPT) line-to-line voltage ranges, ensuring stable signal fidelity during transient excitation events.

Frequently Asked Questions (FAQ)

Q: How is the EXAM module linked to the Exciter Ground Detector Module (EGDM)?

A: Both the EXAM and EGDM units interface through the Exciter Power Backplane (EPBP). The EXAM connects via a 9-pin cable, while the EGDM units utilize the 96-pin P2 connector on the same backplane.

Q: What are the criteria for selecting jumper settings JP1 and JP2?

A: Jumper settings must be configured based on the PPT line-to-line voltage. Use specific configurations for voltages below 750 V rms and separate settings for voltages exceeding 750 V rms to ensure proper attenuation characteristics.

Field Installation Guidelines

  • Cabinet Placement: The module is designed for installation within the High Voltage Interface (HVI) section of the auxiliary cabinet. Ensure adequate clearance for the 9-pin cable routing to avoid signal crosstalk.
  • Jumper Verification: Before applying power to the bridge, verify the JP1 and JP2 jumper positions match the system-specific PPT input voltage requirements. Incorrect settings may lead to signal saturation or damage to downstream EGDM components.
  • Grounding and Shielding: To maintain precise feedback monitoring, ensure the module chassis is firmly bonded to the cabinet ground. Shielded cabling should be used for all inputs derived from the field bus to mitigate high-frequency interference.
  • Connection Integrity: Ensure the 9-pin cable to the EPBP is fully seated. Given the high-voltage nature of the input signals, verify all terminal connections are tightened to prevent arcing and resistive heating.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

The transition of a Programmable Logic Controller (PLC) cabinet from a controlled factory floor to a volatile plant environment represents a critical milestone in factory automation. While a Factory Acceptance Test (FAT) validates standalone hardware compliance under ideal conditions, it cannot replicate real-world process dynamics. Therefore, deploying an industrial automation system requires a rigorous Site Acceptance Test (SAT) to verify total loop integrity, field wiring wiring metrics, and process control parameters before final customer handover.

Read more
Advanced Integration: Master Protocol for VFD Commissioning and Testing

Advanced Integration: Master Protocol for VFD Commissioning and Testing

Deploying variable frequency drives (VFDs) requires precise execution during the initial commissioning phase. Junior automation engineers often find the first power-up sequence intimidating. However, following a rigorous engineering framework ensures equipment safety and system reliability. Proper startup procedures protect both the drive electronics and the connected motor.

Read more
Optimizing Factory Automation: The Definitive Guide to VFD Preventive Maintenance

Optimizing Factory Automation: The Definitive Guide to VFD Preventive Maintenance

Variable Frequency Drives (VFDs) serve as critical assets in modern industrial automation. These power electronic devices regulate electric motors by adjusting the supplied frequency and voltage. Consequently, industries utilize VFDs to reduce energy consumption and optimize process control. Major manufacturers like Siemens, ABB, and Yaskawa design highly efficient drives. However, sustained efficiency requires a rigorous preventive maintenance program.

Read more