Skip to content

What are you looking for?


You may also like

GE IS200TBAIH2C Analog I/O Terminal BoardGE IS200TBAIH2C Analog I/O Terminal BoardGE IS200TBAIH2C Analog I/O Terminal Board
GE IS200TBAIH2C Analog I/O Terminal Board
GE IS200TBAIH2C Analog I/O Terminal Board
GE IS200TBAIH2C Analog I/O Terminal Board

GE IS200TBAIH2C Analog I/O Terminal Board


Only 10 left - Selling fast

PRODUCT SKU : IS200TBAIH2C

PRODUCT TYPE : Analog Input Modules

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE IS200TBAIH2C, also cataloged as the IS200TBAIH2C Analog I/O Terminal Board, operates as a dedicated hardware component for signal termination within Mark VI and Mark VIe turbine control platforms. Configured for integration with the IS220PAIC I/O pack, this terminal board provides direct physical execution of analog input and output signal routing for gas and steam turbine control systems.

Hardware Specifications

Parameter Specification
Model IS200TBAIH2C
Brand GE
Origin USA
Dimensions Standard PCB form factor
Operating Temp Standard industrial ambient range
Power Consumption System-dependent
Core Performance 8 analog I/O configurations; Simplex/TMR support

Industrial Control and Firmware Compatibility

The IS200TBAIH2C supports a total of eight distinct analog I/O configurations, enabling interface flexibility for diverse field instrumentation. Supported signal types include 0-20 mA and 4-20 mA current inputs, externally powered transmitter inputs, 0-20 mA analog outputs, and +/- 5 VDC or +/- 10 VDC voltage inputs. A specialized 0-200 mA analog output mode is available exclusively when paired with the IS220PAICH2 I/O pack. The board maintains firmware flash compatibility via the host PAIC I/O pack, ensuring that signal processing logic is updated in accordance with the system control software (GEH-6721/GEH-6723). The TBAI module is designed for I/O density scaling in both Simplex and Triple Modular Redundant (TMR) architectures, providing the physical layer for distributed I/O management.

Frequently Asked Questions

Q: Is the IS200TBAIH2C compatible with I/O packs other than the IS220PAIC?

A: No. The H2C revision is specifically engineered for connection to the IS220PAIC analog I/O pack. Compatibility with other packs, such as older YAIC variants, is not supported for this specific hardware revision.

Q: Can this terminal board be deployed in Simplex and TMR configurations?

A: Yes. The IS200TBAIH2C is designed for use in both Simplex and Triple Modular Redundant (TMR) systems. Configuration details for TMR implementation are documented in the GEH-6721 technical manual.

Field Installation Guidelines

  • Mounting: Secure the board within the cabinet using the provided mounting points. Ensure proper alignment with the backplane connectors to prevent mechanical stress on the PCB.
  • Wiring: Route analog signal cabling through shielded, twisted-pair paths. Connect shields to the dedicated cabinet ground bus to mitigate electromagnetic interference and maintain measurement accuracy for low-level voltage inputs.
  • Termination: Ensure all wire terminations are tightened to the specified torque. Avoid over-tightening terminal screws to prevent damage to the terminal block inserts or underlying PCB traces.
  • Verification: Prior to system energization, perform a point-to-point continuity check to verify that field device wiring correctly maps to the designated I/O channel terminals. Confirm that the I/O pack is properly seated and locked in position.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

UPS architecture dictates power reliability in process automation. Unplanned voltage sags cause immediate downtime, making robust power backup essential for PLC and DCS networks. This technical guide evaluates the operational principles, key architectures, and tradeoffs between Static and Dynamic Rotary UPS systems.
Read more
Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Signal integrity determines reliability in modern industrial automation. Unwanted electrical noise degrades sensor data, distorts 4-20 mA current loops, and drops fieldbus communications. Engineers working with PLC, DCS, and TSI systems must effectively mitigate these disturbances. This technical guide analyzes key internal and external noise sources affecting control systems.
Read more
Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Emergency stop (E-Stop) pushbuttons serve as vital safety devices in factory automation and process control plants. Functional safety standards mandate normally-closed (NC) contact blocks to ensure fail-safe operation during wiring breaks or power outages. However, mechanical degradation over time can trigger unexpected spurious trips, halting production lines without an actual emergency. Understanding the underlying causes of mechanical contact failure allows automation engineers to implement robust, fault-tolerant safety circuits.

Read more