PRODUCT SKU : IC693BEM331K

PRODUCT TYPE : Communication Modules

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE Fanuc IC693BEM331K, also cataloged as the IC693BEM331 Genius Bus Controller, operates as a dedicated hardware component for serial bus communication execution between the Series 90-30 PLC backplane and Genius I/O field networks.

Hardware Specifications

Parameter Specification
Model IC693BEM331K
Brand GE Fanuc
Origin USA
Weight 0.38 kg (0.84 lbs)
Dimensions Single-slot Series 90-30 format
Operating Temp 0 to 60 deg C
Power Consumption 1.5 W (300 mA at 5 VDC)
Product Line Series 90-30
Device Capacity Up to 31 devices on Genius I/O bus
Maximum Data Payload Up to 128 bytes send/receive control data
Backplane Draw 300 mA from 5 VDC bus
Network Protocol Genius I/O serial bus / Global Data
Hardware Compatibility Series 90-30 PLC racks, Genius Blocks, Field Control BIU

Backplane Bus Communication & Firmware Integration

The module negotiates control data transfer across the local Series 90-30 backplane bus to ensure predictable communication velocity between CPU sweep cycles and remote Genius nodes. The board logic converts high-density backplane I/O traffic into serial datagrams, coordinating up to 128 bytes of input and output transfer sequences across 31 Genius I/O bus addresses.

I/O density scaling allows integration with Genius discrete blocks, analog blocks, and Field Control I/O stations equipped with Bus Interface Units (BIU). Firmware flash compatibility ensures persistent configuration storage for I/O scanning modes, enhanced diagnostic commands, and Global Data broadcast routines without requiring onboard battery retention.

Frequently Asked Questions

Q: How is physical line verification managed on the Genius bus without relying on 90-70 style fault table counts?

A: Verification of configuration integrity is executed by evaluating the GBC Device Present status bit within the PLC application logic, rather than relying on fault table configuration error counts.

Q: What are the backplane power supply draw limits for the module when installed in a Series 90-30 chassis?

A: The module draws 300 mA from the +5 VDC supply rail provided through the Series 90-30 baseplate backplane connector during standard operation.

Q: Can the module be inserted or removed while the Series 90-30 rack is powered on?

A: No. System power to the baseplate rack must be disconnected before installing or extracting the module to prevent damage to the backplane edge connectors and logical disruptions on the active bus.

Field Installation Guidelines

  1. Power Shutdown: Turn off all primary AC/DC system power supplying the Series 90-30 baseplate before inserting the module into its designated slot.
  2. Backplane Insertion: Align the rear circuit card edges with the plastic card guides of the selected chassis slot. Slide the card backward until the backplane connector locks firmly into place.
  3. Serial Bus Wiring: Connect the shielded twisted-pair Genius serial bus cable to the front terminal assembly. Ensure proper daisy-chain topology across all 31 potential device drops on the line.
  4. Shield Grounding: Terminate the cable shield drain wire directly to the chassis ground terminal to maintain signal integrity and prevent noise coupling on serial differential lines.
  5. Bus Line Termination: Install standard 75-ohm or 100-ohm line terminating resistors across the physical serial tap terminals at the two physical ends of the Genius network trunk.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Redundant Automation Systems: Maximizing Uptime in Critical Control Applications

Redundant Automation Systems: Maximizing Uptime in Critical Control Applications

Industrial automation relies on continuous operational stability to prevent catastrophic downtime and financial loss. While standard dictionary definitions treat redundancy as superfluous, industrial engineers consider redundant control architectures indispensable for high-availability systems. Implementing backup hardware ensures seamless takeover during primary equipment failures, protecting critical infrastructure across manufacturing and process industries.

Read more
Demystifying the 5 Levels of Industrial Automation Architecture

Demystifying the 5 Levels of Industrial Automation Architecture

Modern manufacturing relies on structured communication hierarchy to bridge physical shop-floor hardware with enterprise management software. This framework, commonly known as the Automation Pyramid, establishes how data flows between field devices, logic controllers, and corporate IT networks. Understanding these five distinct levels helps engineers and plant managers optimize system operations, reduce downtime, and implement seamless factory automation solutions.

Read more
Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Manufacturing Execution Systems serve as the digital backbone of modern factory floors. Positioned at Level 3 of the ISA-95 automation pyramid, MES links enterprise resource planning with real-time shop floor control systems. Today, industrial operators rely on MES software to bridge operational strategy with physical production execution.

Read more