Skip to content

What are you looking for?


You may also like

GE IC200MDL750H VersaMax Discrete Output ModuleGE IC200MDL750H VersaMax Discrete Output ModuleGE IC200MDL750H VersaMax Discrete Output Module
GE IC200MDL750H VersaMax Discrete Output Module
GE IC200MDL750H VersaMax Discrete Output Module
GE IC200MDL750H VersaMax Discrete Output Module

GE IC200MDL750H VersaMax Discrete Output Module


Only 10 left - Selling fast

PRODUCT SKU : IC200MDL750H

PRODUCT TYPE : Discrete Output Modules

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE IC200MDL750H, also cataloged as the IC200MDL750 Discrete Output Module, operates as a dedicated hardware component for 12/24 VDC solid-state switching and direct actuator load drive within GE VersaMax control platforms.

Hardware Specifications

Parameter Specification
Model IC200MDL750H
Brand GE (GE Fanuc / Emerson)
Origin USA
Weight 0.90 kg (1.98 lbs)
Operating Temp 0 to 30 deg C
Power Consumption 90 mA max backplane current draw; external 10.2 to 30 VDC field supply
Output Channels 32 sourcing-type channels (2 groups of 16 channels)
Nominal Output Voltage 12/24 VDC
Output Voltage Range 10.2 to 30 VDC
Output Current Rating 0.5 A per channel
Inrush Current 2.0 A max per point for 100 ms
Response Time ON: 0.2 ms; OFF: 1.0 ms
Status Indicators Individual channel status LEDs, OK LED, FLD PWR LED
Internal Protection No internal fuses
Hazardous Location Class I Division 2 certified

Deterministic Network Execution & Backplane Velocity

The IC200MDL750H transfers digital logic states across the VersaMax backplane bus, drawing up to 90 mA from the backplane power supply rail. Internal driver circuits process 32 sourcing-type outputs organized into two isolated groups of 16 channels, providing fast response times of 0.2 ms ON and 1.0 ms OFF.

Integration into Profinet / EtherNet/IP deterministic networks via primary communication interfaces guarantees low network latency and rapid update rates across local and expanded racks. System-wide firmware flash compatibility maintains consistent cycle timing during real-time scan execution, enabling seamless I/O density scaling across complex multi-chassis architectures.

Frequently Asked Questions

Q: Does the IC200MDL750H module feature internal overcurrent fusing on the output channels?

A: No. The IC200MDL750H contains no internal output fuses. External fuse protection must be provided on field wiring lines to prevent circuit damage from short circuit conditions.

Q: What are the backplane current draw and external field power requirements for this module?

A: The logic interface draws a maximum of 90 mA from the rack backplane power supply, while output loads require an external nominal 12/24 VDC (10.2 to 30 VDC) field power source.

Q: What inrush current capacity can an individual output point tolerate?

A: Each individual output point can handle a maximum surge inrush current of 2.0 A for up to 100 ms during inductive or lamp load switching.

Field Installation Guidelines

  1. Power Shutdown: De-energize all primary rack backplane power supplies and external 12/24 VDC field power sources prior to module mounting or terminal carrier handling.
  2. DIN-Rail Mounting: Mount the module carrier onto a standard 35 mm DIN rail, securing all panel grounding clips to maintain proper cabinet chassis earth connection.
  3. Field Wiring Procedure: Connect external 10.2 to 30 VDC positive logic supplies to the field power input terminals. Route individual channel conductors to loads using appropriate wire gauges.
  4. Inductive Suppression: Install external flyback diodes or RC suppression networks directly across inductive field loads (such as DC solenoids or contactor coils) to suppress voltage transients.
  5. ESD Safeguards: Wear a grounded anti-static wrist strap connected to a clean cabinet metallic earth during installation to prevent static damage to logic components.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying the 5 Levels of Industrial Automation Architecture

Demystifying the 5 Levels of Industrial Automation Architecture

Modern manufacturing relies on structured communication hierarchy to bridge physical shop-floor hardware with enterprise management software. This framework, commonly known as the Automation Pyramid, establishes how data flows between field devices, logic controllers, and corporate IT networks. Understanding these five distinct levels helps engineers and plant managers optimize system operations, reduce downtime, and implement seamless factory automation solutions.

Read more
Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Manufacturing Execution Systems serve as the digital backbone of modern factory floors. Positioned at Level 3 of the ISA-95 automation pyramid, MES links enterprise resource planning with real-time shop floor control systems. Today, industrial operators rely on MES software to bridge operational strategy with physical production execution.

Read more
Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Industrial Ethernet forms the backbone of factory automation. Selecting the right switch architecture determines system uptime, data throughput, and OT cyber resilience. This technical guide evaluates managed vs. unmanaged switches, analyzing operational differences, security controls, and selection criteria.
Read more