Overview
The IC695ALG728 from GE Fanuc is an analog output module in the RX3i PACSystem series, designed for precision signal conversion with channel-to-channel isolation. It supports multiple voltage and current ranges, configurable filtering, and flexible data formats suitable for industrial process control applications.

Key Specifications

  • Module Type: Analog Output, non-isolated

  • Channels: 8 single-ended or 4 differential outputs

  • Current Output Range: 0–20 mA, 4–20 mA, ±20 mA

  • Voltage Output Range: ±10 V, 0–10 V, ±5 V, 0–5 V, 1–5 V

  • Resolution: 24-bit ADC converted to floating point or integer

  • Configurable Filters: 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, 500 Hz

  • Internal Power: 3.3 V @ 450 mA, 5 V @ 600 mA

  • Data Format: IEEE 32-bit floating point or 16-bit integer in 32-bit field

  • Operating Temperature: 0–60 °C (32–140 °F)

  • Storage Temperature: -40–85 °C (-40–185 °F)

  • Input Impedance: >100 kΩ for voltage inputs

  • Maximum Overvoltage: ±60 VDC continuous

  • Maximum Overcurrent: ±28 mA continuous

  • Backplane Power Consumption: 330 mA max @ 5 V, 600 mA max @ 3.3 V

  • Power Dissipation: 4.83 W maximum

  • Open Circuit Detection: ≤1 second

  • Programmer Version: Compatible with Machine Edition v5.0 SP3 and later

  • Weight: 0.31 kg (0.69 lbs)

Applications
Ideal for controlling analog actuators, process loops, and industrial devices where precise voltage or current output is required. The module is suitable for both factory automation and advanced process control environments.

FAQ
Q: Can the IC695ALG728 handle both single-ended and differential outputs?
A: Yes, it supports 8 single-ended or 4 differential channels.

Q: What communication software is supported?
A: Compatible with Machine Edition v5.0 SP3 or later for configuration and control.

Q: What is the maximum temperature for safe operation?
A: Up to 60 °C (140 °F).

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying PLC Memory: A Technical Guide to Architecture, Retention, and Performance

Demystifying PLC Memory: A Technical Guide to Architecture, Retention, and Performance

Modern industrial automation relies heavily on the reliability of programmable logic controllers (PLCs). At the heart of every PLC lies its memory system. This subsystem directly dictates scan times, program capacity, and data survival during power outages. For field engineers, understanding how a control system allocates, retains, and secures this memory is essential for writing efficient code and preventing costly downtime.

Read more
Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

The transition of a Programmable Logic Controller (PLC) cabinet from a controlled factory floor to a volatile plant environment represents a critical milestone in factory automation. While a Factory Acceptance Test (FAT) validates standalone hardware compliance under ideal conditions, it cannot replicate real-world process dynamics. Therefore, deploying an industrial automation system requires a rigorous Site Acceptance Test (SAT) to verify total loop integrity, field wiring wiring metrics, and process control parameters before final customer handover.

Read more
Advanced Integration: Master Protocol for VFD Commissioning and Testing

Advanced Integration: Master Protocol for VFD Commissioning and Testing

Deploying variable frequency drives (VFDs) requires precise execution during the initial commissioning phase. Junior automation engineers often find the first power-up sequence intimidating. However, following a rigorous engineering framework ensures equipment safety and system reliability. Proper startup procedures protect both the drive electronics and the connected motor.

Read more