PRODUCT SKU : DS200DTBCG1A

PRODUCT TYPE : Contact Output Termination Modules

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE DS200DTBCG1A, also cataloged as the DS200DTBCG1A Contact Output Termination Module, operates as a dedicated hardware component for relay signal termination and solenoid control within the Mark V control system.

Hardware Specifications

Parameter Specification
Model DS200DTBCG1A
Brand General Electric
Origin United States (USA)
Series Mark V
Product Type Contact Output Termination Module
Weight Subject to final enclosure configuration
Dimensions Standard Mark V PCB footprint
Operating Temp Industrial standard 0 to 60 deg C
Power Consumption Dependent on connected solenoid load

Industrial Control & Firmware Compatibility

The DS200DTBCG1A functions as the terminal interface for the TCRA relay board. The module supports backplane bus communication and I/O density scaling by facilitating connections across the Q11, Q21, and Q51 cores. Hardware jumpers on the module enable the configuration of 18 out of the 30 available outputs in the Q51 core for solenoid actuation. In the Q11 core configuration, jumper settings are specifically mapped to support gas manifold blow-off valve control sequences, ensuring deterministic response times for critical output operations.

Frequently Asked Questions

Q: Are the contact outputs on the DS200DTBCG1A hot-swappable?

A: No. The Mark V architecture does not support hot-swapping for the DTBC termination module. The system must be de-energized prior to removing or installing the board to prevent electrical arc damage to the backplane connectors.

Q: How is 125 V DC power supplied to the contact outputs?

A: Power is routed via the J15/J16 connectors linked to the TCPD board in the PD core. Specific configuration in the Q51 core allows for 125 V DC distribution to outputs 16, 17, and 18.

Field Installation Guidelines

  • Connector Integrity: Verify that JS1-JS8 connectors are securely seated to ensure reliable signal acquisition from the TCRA board.
  • Jumper Configuration: Ensure P1/M1 through P18/M18 jumpers are correctly aligned. In solenoid-enabled configurations, both P and M jumpers must be installed or removed simultaneously to prevent open-circuit faults.
  • Grounding: Maintain clean contact surfaces at mounting points to ensure chassis ground continuity.
  • Cable Routing: Separate signal-level wiring (JS1-JS8) from solenoid power supply wiring (J8) to mitigate electromagnetic interference (EMI) on the relay control paths.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

The transition of a Programmable Logic Controller (PLC) cabinet from a controlled factory floor to a volatile plant environment represents a critical milestone in factory automation. While a Factory Acceptance Test (FAT) validates standalone hardware compliance under ideal conditions, it cannot replicate real-world process dynamics. Therefore, deploying an industrial automation system requires a rigorous Site Acceptance Test (SAT) to verify total loop integrity, field wiring wiring metrics, and process control parameters before final customer handover.

Read more
Advanced Integration: Master Protocol for VFD Commissioning and Testing

Advanced Integration: Master Protocol for VFD Commissioning and Testing

Deploying variable frequency drives (VFDs) requires precise execution during the initial commissioning phase. Junior automation engineers often find the first power-up sequence intimidating. However, following a rigorous engineering framework ensures equipment safety and system reliability. Proper startup procedures protect both the drive electronics and the connected motor.

Read more
Optimizing Factory Automation: The Definitive Guide to VFD Preventive Maintenance

Optimizing Factory Automation: The Definitive Guide to VFD Preventive Maintenance

Variable Frequency Drives (VFDs) serve as critical assets in modern industrial automation. These power electronic devices regulate electric motors by adjusting the supplied frequency and voltage. Consequently, industries utilize VFDs to reduce energy consumption and optimize process control. Major manufacturers like Siemens, ABB, and Yaskawa design highly efficient drives. However, sustained efficiency requires a rigorous preventive maintenance program.

Read more