The GE D20 MIC 10BASE-T 820-0756, also cataloged as the 820-0756 Ethernet Interface Module, operates as a dedicated hardware component for LAN media conversion and 10 Mbps Ethernet signal conditioning within GE D20 Substation Automation platforms.

Hardware Specifications

Parameter Specification
Model 820-0756
Brand GE
Origin USA
Platform D20 Substation Automation Systems
Module Type Media Interface Controller (MIC)
Port Type 10BASE-T Ethernet (RJ45 / AUI media conversion)
Physical Media Category 3/5 Unshielded Twisted Pair (UTP)
Data Transfer Rate 10 Mbps (half-duplex / full-duplex execution)
Dimensions Standard D20 rack card profile
Weight 0.4 kg
Operating Temp -20 to +70 deg C
Power Consumption 2.5 W (typical, backplane powered)

Backplane Bus Communication & I/O Density Scaling

The interface card routes 10BASE-T network frames into the internal D20 backplane architecture, supporting deterministic protocol translation and sequence-of-events reporting. Internal logic buffering regulates network packet queues to prevent frame collision backpressure from delaying local SCADA task execution. The onboard transceiver isolates logic ground loops while maintaining continuous signal integrity across expanded substation network topologies.

Frequently Asked Questions

Q: What network medium does the 820-0756 module interface with?

A: The module provides direct physical conversion to 10BASE-T twisted-pair Ethernet media over an standard RJ45 copper interface at 10 Mbps transmission speeds.

Q: How is operating power delivered to the media controller board?

A: Operational logic power is drawn directly from the internal D20 chassis backplane bus, requiring no external auxiliary power wiring.

Q: How are channel signal lines protected against station ground potential rise?

A: Channel-to-bus galvanic isolation transformers isolate field network cabling from the core processor backplane to prevent ground potential interference.

Field Installation Guidelines

  1. Power down the host D20 chassis or verify hot-swap rack procedure compliance before sliding the card into its designated slot.
  2. Align the module card edges with the internal card guides and push firmly until the rear connector seats into the backplane socket.
  3. Tighten the front panel retaining screws to a torque specification of 0.6 Nm to ensure mechanical retention and frame grounding.
  4. Plug the CAT3/CAT5 STP or UTP network cable into the RJ45 port until the retention tab locks securely.
  5. Ensure Ethernet signal cables are dressed away from high-voltage DC control circuits and switching transformer lines.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying the 5 Levels of Industrial Automation Architecture

Demystifying the 5 Levels of Industrial Automation Architecture

Modern manufacturing relies on structured communication hierarchy to bridge physical shop-floor hardware with enterprise management software. This framework, commonly known as the Automation Pyramid, establishes how data flows between field devices, logic controllers, and corporate IT networks. Understanding these five distinct levels helps engineers and plant managers optimize system operations, reduce downtime, and implement seamless factory automation solutions.

Read more
Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Manufacturing Execution Systems serve as the digital backbone of modern factory floors. Positioned at Level 3 of the ISA-95 automation pyramid, MES links enterprise resource planning with real-time shop floor control systems. Today, industrial operators rely on MES software to bridge operational strategy with physical production execution.

Read more
Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Industrial Ethernet forms the backbone of factory automation. Selecting the right switch architecture determines system uptime, data throughput, and OT cyber resilience. This technical guide evaluates managed vs. unmanaged switches, analyzing operational differences, security controls, and selection criteria.
Read more