Configured for analog signal acquisition in Yokogawa CENTUM VP and ProSafe-RS platforms, the Yokogawa A2SAM105-H000 (A2SAM105 Analog Input Adapter) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model A2SAM105-H000
Brand Yokogawa
Origin Japan
Input Types 4-20 mA DC, 1-5 V DC, 0-10 V DC
Allowable Input Range 0-40 mA, 0-30 V DC
Input Resistance 320 ohm @ 20 mA, 640 ohm @ 4 mA (powered); >=100 kohm (unpowered)
Accuracy +/-4 mV / +/-12 uA @ 23+/-2 deg C; +/-8 mV / +/-24 uA @ 0-60 deg C
Withstanding Voltage 500 V AC for 1 min (I/O adaptors), 42 V DC
Weight 0.10 kg
Dimensions Compact plug-in, baseplate mounted
Operating Temp 0 to 60 deg C
Power Consumption Powered via baseplate 5 V DC rail
Diagnostics Open/short circuit detection, internal self-test
Redundancy Simplex or TMR compatible
Safety Certification Up to SIL3 (IEC 61508)
Protocol HART 7 digital overlay

Yokogawa Channel-to-Channel Isolation & DCS Signal Integrity

Yokogawa N-IO analog architectures use galvanic channel-to-channel isolation to block circulating ground currents across distributed sensor points. Maintaining continuous isolation integrity protects the internal signal paths when processing 4-20 mA HART loop protocol parameters alongside 1-5 V DC or 0-10 V DC voltage inputs. Dedicated isolation barriers uphold a 500 V AC withstand threshold, preventing high-frequency common-mode noise from distorting conversion accuracy or degrading downstream controller processing across CENTUM VP and ProSafe-RS field nodes.

Frequently Asked Questions

Q: What is the input resistance behavior of the A2SAM105-H000 during powered versus unpowered conditions?

A: Under powered conditions, the input resistance measures 320 ohm at 20 mA and 640 ohm at 4 mA. When unpowered, the adapter transitions to a high-impedance state measuring >=100 kohm.

Q: What isolation voltage rating does the adapter sustain between channel circuitry and the N-IO backplane?

A: The adapter maintains a dielectric withstand rating of 500 V AC for 1 minute between individual I/O adapter channels and the backplane structure.

Field Installation Guidelines

Insert the adapter vertically into the designated N-IO baseplate slot until the locking tab fully seats onto the backplane. Ensure field wiring terminals are de-energized prior to seating or unseating the hardware. Ground all signal cable shields at a single chassis earth point on the baseplate assembly to limit ground potential differences across analog loops.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying Open Platform Communication (OPC): The Backbone of Industrial Interoperability

Demystifying Open Platform Communication (OPC): The Backbone of Industrial Interoperability

Interoperability remains a cornerstone requirement for modern smart factories and process automation. Open Platform Communication (OPC) bridges the gap between disparate hardware platforms, control systems, and visualization software. By establishing a universal communication standard, OPC allows field controllers, SCADA platforms, and enterprise software from different vendors to exchange real-time data seamlessly.

Read more
Understanding Siemens PLC Memory Cards: MMC, SMC, and SD Solutions in Industrial Automation

Understanding Siemens PLC Memory Cards: MMC, SMC, and SD Solutions in Industrial Automation

Memory management plays a pivotal role in maintaining control system reliability across modern manufacturing plants. Industrial control systems rely on specialized memory cards to store project logic, firmware updates, and retentive system data. Siemens uses several memory architectures, including Micro Memory Cards (MMC) and SIMATIC Memory Cards (SMC). Engineers must understand these hardware variations to ensure zero data loss and minimize downtime during maintenance routines.

Read more
Redefining Control Systems: The Rise of Flexible I/O Modules in Industrial Automation

Redefining Control Systems: The Rise of Flexible I/O Modules in Industrial Automation

Conventional input-output architectures often limit engineering agility and inflate long-term inventory costs. Today, Flexible Input/Output Modules (FIOM) are transforming how control system engineers design, commission, and maintain automation infrastructure. By allowing individual channel software configuration, FIOM technology bridges the gap between rigid hardware design and dynamic plant requirements.

Read more