Overview
The TC-IDD321 is a 32-channel Digital Input Module engineered for Honeywell Experion LS and compatible control platforms. Its high-density design captures discrete DC signals from field devices, offering reliable monitoring for sensors, pushbuttons, limit switches, and other industrial inputs. The rugged construction ensures durability in harsh industrial environments while maintaining ease of installation and maintenance.

Specifications

  • Model & Part Number: TC-IDD321

  • Product Type: Digital Input I/O Module

  • Number of Inputs: 32 (organized as 2 groups of 16 points)

  • Input Voltage Range: 10–31.2 VDC at 60°C

  • Nominal Input Voltage: 24 VDC

  • On-State Current (Minimum): 2 mA

  • Off-State Voltage (Maximum): 5 V

  • Off-State Current (Maximum): 1.5 mA

  • Isolation Voltage:

    • Channel-to-channel: 1500 VDC, tested 1 second

    • User-to-system: 1500 VDC, tested 1 second

  • Input Delay Time:

    • Off-to-on: Hardware delay, programmable filter 1 ms or 2 ms

    • On-to-off: Hardware delay, programmable filter 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

  • Power Dissipation: 6.1 W maximum

  • Short/Inrush Current: 250 mA peak (decays to <37% in 22 ms, without activation)

  • Input Compatibility: IEC Type 1+

  • Backplane Current: See module power consumption data

  • Connection Terminal Block: TC-TBCH, 36-position terminal block

  • Operating Environment: Designed for industrial environments with temperature and vibration tolerance

Features

  • High-Density Input: 32 channels allow compact I/O integration

  • Rugged Design: Engineered for harsh industrial conditions

  • Easy Installation: Standard terminal blocks for quick wiring

  • Wide PLC Compatibility: Works with Experion LS, Allen-Bradley, Siemens, Rockwell, and other PLCs

  • Reliable Isolation: Safe operation with channel-to-channel and system isolation

  • Programmable Filters: Customizable input delay to reduce signal noise

Applications
Ideal for distributed control systems, factory automation, process control, and monitoring discrete field devices. Compatible with legacy and modern PLC environments.

FAQ

Q: How many input channels does TC-IDD321 provide?
A: 32 discrete channels organized into 2 isolated groups.

Q: What voltage range is supported?
A: 10–31.2 VDC with a nominal 24 VDC operation.

Q: Is this module compatible with other PLC systems?
A: Yes, it works with Experion LS, Allen-Bradley, Siemens, Rockwell, and other major PLCs.

Q: Does it include galvanic isolation?
A: Yes, channel-to-channel and user-to-system isolation is tested at 1500 VDC.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

UPS architecture dictates power reliability in process automation. Unplanned voltage sags cause immediate downtime, making robust power backup essential for PLC and DCS networks. This technical guide evaluates the operational principles, key architectures, and tradeoffs between Static and Dynamic Rotary UPS systems.
Read more
Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Signal integrity determines reliability in modern industrial automation. Unwanted electrical noise degrades sensor data, distorts 4-20 mA current loops, and drops fieldbus communications. Engineers working with PLC, DCS, and TSI systems must effectively mitigate these disturbances. This technical guide analyzes key internal and external noise sources affecting control systems.
Read more
Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Emergency stop (E-Stop) pushbuttons serve as vital safety devices in factory automation and process control plants. Functional safety standards mandate normally-closed (NC) contact blocks to ensure fail-safe operation during wiring breaks or power outages. However, mechanical degradation over time can trigger unexpected spurious trips, halting production lines without an actual emergency. Understanding the underlying causes of mechanical contact failure allows automation engineers to implement robust, fault-tolerant safety circuits.

Read more