Skip to content

What are you looking for?


You may also like

Honeywell 8C-TDIL01 8U-TDIL01 51306856-175 C300 Digital Input ModuleHoneywell 8C-TDIL01 8U-TDIL01 51306856-175 C300 Digital Input ModuleHoneywell 8C-TDIL01 8U-TDIL01 51306856-175 C300 Digital Input Module
Honeywell 8C-TDIL01 8U-TDIL01 51306856-175 C300 Digital Input Module
Honeywell 8C-TDIL01 8U-TDIL01 51306856-175 C300 Digital Input Module
Honeywell 8C-TDIL01 8U-TDIL01 51306856-175 C300 Digital Input Module

Honeywell 8C-TDIL01 8U-TDIL01 51306856-175 C300 Digital Input Module


Only 10 left - Selling fast

PRODUCT SKU : 8C-TDIL01 8U-TDIL01 51306856-175

PRODUCT TYPE : Digital Input Modules

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for discrete signal acquisition and contact status sensing in Experion PKS C300 systems, the Honeywell 51306856-175 (8C-TDIL01 / 8U-TDIL01 Digital Input Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model 51306856-175 (8C-TDIL01 / 8U-TDIL01)
Brand Honeywell
Origin USA
Weight ~0.31 kg (Logic Module), ~140 g (IOTA)
Dimensions 20.2 cm x 14.4 cm x 4.9 cm (Logic), 118 mm x 32 mm x 87 mm (IOTA)
Operating Temp -40 deg C to +70 deg C
Power Consumption Max 3.2 W
Input Channels 16 independent channels
Rated Input Voltage 24 VDC
Input Voltage Range 18 to 30 VDC
Input Current Max 6 mA per channel
Response Time < 8 ms
Isolation Voltage 1500 VAC

Channel-to-Channel Isolation & Cold Junction Compensation (CJC)

The module integrates 16 optocoupler-isolated digital input channels rated for 24 VDC operation across an input range of 18 to 30 VDC. The 1500 VAC galvanic isolation barrier decouples field wiring loops from internal processing logic, blocking transient voltage spikes and ground loop currents. Inputs achieve a response time under 8 ms while drawing a maximum current of 6 mA per channel, enabling deterministic status detection for limit switches, proximity sensors, and contact closures directly routed through the Series 8 backplane.

Frequently Asked Questions

Q: What is the maximum signal propagation delay for field contact inputs through the 8C-TDIL01 module?

A: The module processes input state transitions with a total response time under 8 ms.

Q: Can the 8C-TDIL01 logic module be replaced without disturbing field wiring connections?

A: Yes, field wiring terminates directly at the 8U-TDIL01 IOTA, allowing the 8C-TDIL01 logic module to be unseated independently during maintenance.

Q: What isolation voltage rating protects the controller logic from field side electrical surges?

A: The module provides optocoupler isolation rated at 1500 VAC between field input terminals and internal system logic.

Field Installation Guidelines

  1. Ensure power to the 8U-TDIL01 IOTA carrier base is turned off before mounting or unseating the 8C-TDIL01 logic module.
  2. Wear an ESD wrist strap connected to cabinet earth ground during module handling and installation.
  3. Align the 8C-TDIL01 logic card with the terminal assembly guides and press evenly until retention screws can be securely fastened.
  4. Keep 24 VDC input wiring separated from high-voltage AC power cabling in control enclosure ducting to limit electromagnetic interference.
  5. Connect input cable shields to a dedicated earth ground bar at a single termination point.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Signal integrity determines reliability in modern industrial automation. Unwanted electrical noise degrades sensor data, distorts 4-20 mA current loops, and drops fieldbus communications. Engineers working with PLC, DCS, and TSI systems must effectively mitigate these disturbances. This technical guide analyzes key internal and external noise sources affecting control systems.
Read more
Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Emergency stop (E-Stop) pushbuttons serve as vital safety devices in factory automation and process control plants. Functional safety standards mandate normally-closed (NC) contact blocks to ensure fail-safe operation during wiring breaks or power outages. However, mechanical degradation over time can trigger unexpected spurious trips, halting production lines without an actual emergency. Understanding the underlying causes of mechanical contact failure allows automation engineers to implement robust, fault-tolerant safety circuits.

Read more
Redundant Automation Systems: Maximizing Uptime in Critical Control Applications

Redundant Automation Systems: Maximizing Uptime in Critical Control Applications

Industrial automation relies on continuous operational stability to prevent catastrophic downtime and financial loss. While standard dictionary definitions treat redundancy as superfluous, industrial engineers consider redundant control architectures indispensable for high-availability systems. Implementing backup hardware ensures seamless takeover during primary equipment failures, protecting critical infrastructure across manufacturing and process industries.

Read more