The Foxboro P0918AH, also cataloged as the P0918AH Analog Input Module, operates as a dedicated hardware component for high-density analog signal digitization and real-time process monitoring within Foxboro DCS platforms. It processes 16 analog input channels across current and voltage ranges, converting field signals into 16-bit digital resolution for system controller execution.

Hardware Specifications

Parameter Specification
Model P0918AH
Brand Foxboro
Origin USA
Weight 0.45 kg
Dimensions 172 mm x 107 mm x 61 mm
Operating Temp -40 deg C to +70 deg C
Power Consumption 3.5 W
Input Channels 16 analog inputs
Input Signal Types Current: 4-20 mA; Voltage: 0-10 V, -10 V to +10 V
Resolution 16 bits
Accuracy +-0.1% of full scale
Isolation Voltage 500 VDC between channels
Power Supply 24 VDC
Update Rate 250 ms response time

Channel-to-Channel Isolation and Loop Protocol Integration

The Foxboro P0918AH incorporates 500 VDC galvanic isolation barriers between individual channels to maintain signal integrity and eliminate ground loops across field wiring. This channel-to-channel isolation safeguards 16-bit analog-to-digital conversions against common-mode electrical noise and high-voltage transients while processing 4-20 mA HART loop protocol transmitters and multi-range voltage instruments.

Frequently Asked Questions

Q: What isolation rating is provided between individual channels on the P0918AH module?

A: The P0918AH provides 500 VDC galvanic isolation between input channels to protect logic circuits against potential ground fault currents.

Q: What is the sampling update rate across all 16 channels of the P0918AH module?

A: The module executes a maximum response time of 250 ms across its input channels for real-time control loop updating.

Field Installation Guidelines

Mount the P0918AH module vertically into its designated baseplate card slot, verifying that upper and lower mechanical retention clips engage fully with the chassis rails. Ensure 24 VDC system supply power is de-energized prior to seating or removing the module.

Route all analog field input wiring through dedicated low-voltage wiring ductwork, physically separated from high-voltage AC cables and motor drives. Connect all signal cable drain shields to the main cabinet single-point ground bar. For conduit penetrations entering the cabinet enclosure, ensure all threaded NPT fittings achieve a minimum of 5 full threads of engagement to maintain physical strain relief and grounding integrity.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Industrial Ethernet forms the backbone of factory automation. Selecting the right switch architecture determines system uptime, data throughput, and OT cyber resilience. This technical guide evaluates managed vs. unmanaged switches, analyzing operational differences, security controls, and selection criteria.
Read more
Hot Standby vs. Cold Standby Redundancy in Industrial Automation

Hot Standby vs. Cold Standby Redundancy in Industrial Automation

System availability determines process safety and productivity in industrial automation. Control engineers deploy redundancy to eliminate single points of failure. This technical guide evaluates Hot Standby vs. Cold Standby architectures, comparing failover speeds, memory sync, cost trade-offs, and field selection criteria.

Read more
ON-OFF Controller vs. PID Controller: Industrial Control System Evaluation

ON-OFF Controller vs. PID Controller: Industrial Control System Evaluation

Selecting the right control strategy impacts process stability, efficiency, and equipment lifespan. This technical comparison evaluates binary ON-OFF and continuous PID control algorithms, analyzing their mathematical behavior, operational differences, and practical selection criteria for factory automation.
Read more