Skip to content

What are you looking for?


You may also like

3BDH000395R0001 ABB CI 773F Communication Interface Module3BDH000395R0001 ABB CI 773F Communication Interface Module3BDH000395R0001 ABB CI 773F Communication Interface Module
3BDH000395R0001 ABB CI 773F Communication Interface Module
3BDH000395R0001 ABB CI 773F Communication Interface Module
3BDH000395R0001 ABB CI 773F Communication Interface Module

3BDH000395R0001 ABB CI 773F Communication Interface Module


Only 10 left - Selling fast

PRODUCT SKU : CI 773F 3BDH000395R0001

PRODUCT TYPE : Communication Modules

PRODUCT VENDOR : ABB


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The ABB CI 773F 3BDH000395R0001, also cataloged as the CI 773F Communication Interface, operates as a dedicated hardware component for PROFIBUS DP Master protocol execution within Freelance DCS and AC 700F system architectures.

Hardware Specifications

Parameter Specification
Model CI 773F (3BDH000395R0001)
Brand ABB
Origin Germany
Weight 0.096 kg
Dimensions 28 mm x 75 mm x 135 mm
Operating Temp -20 to +70 deg C
Power Consumption 1.6 W (80 mA via CPU 24 VDC terminal)
Protocol Support PROFIBUS DP Master
Transmission Rate 9.6 kbit/s to 12 Mbit/s
Physical Interface 9-pin D-Sub connector
Hot Swap Support Supported
Ingress Protection IP20

Deterministic Network Integration and I/O Density Scaling

The CI 773F module manages high-speed PROFIBUS DP Master field bus communications, interfacing directly with local backplane bus communication velocity frameworks to streamline data exchange across Profinet and EtherNet/IP deterministic networks. Optimized internal transceiver architecture permits maximum I/O density scaling across distributed remote nodes, while onboard flash memory maintains full firmware flash compatibility during online CPU parameter updates and bus cycle reconfigurations.

Frequently Asked Questions

Q: Can the CI 773F module be replaced while the system backplane remains powered?

A: Yes, the CI 773F supports hot-swap functionality, allowing removal and insertion on an energized local base unit without disturbing CPU backplane operations.

Q: How is primary operating power supplied to the CI 773F interface?

A: Operating power is drawn directly from the 24 VDC terminal of the host CPU module across the backplane, consuming a typical current of 80 mA.

Q: What physical connector standard is required for field bus wiring?

A: Field bus cabling connects through a standard 9-pin female D-Sub connector supporting RS485 differential signaling up to 12 Mbit/s.

Field Installation Guidelines

  • Isolate or verify loop insulation on field bus cables prior to mating the 9-pin D-Sub connector to prevent transceiver damage.
  • Secure the D-Sub connector retaining screws to ensure continuous ground shield continuity across the metal housing.
  • Verify proper placement of PROFIBUS DP line termination resistors at both physical ends of the RS485 segment.
  • Maintain a minimum clearance of 25 mm above and below the module enclosure to permit natural convective heat dissipation under high ambient load conditions.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Safety Relays in Industrial Automation: Fundamentals, Design Standards, and Fail-Safe Architecture

Safety Relays in Industrial Automation: Fundamentals, Design Standards, and Fail-Safe Architecture

Safety relays form the bedrock of functional safety in modern factory automation, preventing catastrophic equipment failure and protecting plant personnel. While standard electromechanical relays handle basic load switching, they lack the redundant diagnostics required for high-risk industrial environments. Modern industrial automation platforms—including programmable logic controllers (PLCs) and distributed control systems (DCS)—rely on specialized safety relays to monitor field devices and isolate hazards instantly.

Read more
Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Industrial automation integrates speech recognition, IIoT protocols, and NLP with PLCs and DCS to streamline operations. By leveraging advanced edge computing, engineers enable real-time, hands-free control—allowing personnel to manage smart factory processes safely away from hazardous equipment.

Read more
Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Industrial automation has evolved from a simple manufacturing tool into the operational backbone of high-risk sectors. Modern mining operations increasingly rely on advanced control systems, programmable logic controllers (PLCs), distributed control systems (DCS), and artificial intelligence to address deep-underground hazards. By replacing manual labor in high-risk zones, factory automation technologies protect personnel while significantly boosting operational throughput.

Read more