{"product_id":"triconex-3604e-tricon-digital-output-module","title":"Triconex 3604E Tricon Digital Output Module","description":"\u003cp\u003eThe \u003cstrong\u003eTriconex 3604E\u003c\/strong\u003e (also referenced under ordering number 3640E) is a 16-point digital output module engineered for the Tricon Triple Modular Redundancy (TMR) safety platform. Operating at a nominal system voltage of 24 VDC, it converts controller safety logic into discrete output signals to drive field-side final elements.\u003c\/p\u003e\n\u003ch3\u003eOutput Performance and Load Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe module features 16 non-commoned, point-isolated output channels designed to operate across a field voltage range of 22-45 VDC. Each point supports a maximum continuous load current of 2 A, with a surge capability of 10 A for 10 ms. To protect module electronics, field terminations utilize one 2.5 A fast-acting fuse per output point.\u003c\/p\u003e\n\u003ch3\u003eElectrical Isolation and Hardware Identification\u003c\/h3\u003e\n\u003cp\u003eWith a 1500 VDC point-to-point isolation rating, the unit prevents electrical transients from propagating across channels or back to the control system. The physical front panel incorporates a dark blue color code for quick identification in Tricon chassis slots.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e3604E (3640E)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eTriconex\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Category\u003c\/td\u003e\n\u003ctd\u003eDigital Output Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Architecture\u003c\/td\u003e\n\u003ctd\u003eTriple Modular Redundant (TMR)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Output Points\u003c\/td\u003e\n\u003ctd\u003e16, non-commoned\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage Range\u003c\/td\u003e\n\u003ctd\u003e22-45 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Continuous Current\u003c\/td\u003e\n\u003ctd\u003e2 A per point\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSurge Current\u003c\/td\u003e\n\u003ctd\u003e10 A per point for 10 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical Voltage Drop\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 4 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Leakage Current\u003c\/td\u003e\n\u003ctd\u003e2 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePoint Isolation\u003c\/td\u003e\n\u003ctd\u003e1500 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Termination Fuses\u003c\/td\u003e\n\u003ctd\u003e1 per output, 2.5 A fast-acting\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eColor Code\u003c\/td\u003e\n\u003ctd\u003eDark blue\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipping Weight\u003c\/td\u003e\n\u003ctd\u003e5 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What fusing protection is required for field outputs on the Triconex 3604E?\u003c\/p\u003e\n\u003cp\u003eA: Field termination assemblies use individual 2.5 A fast-acting fuses allocated to each of the 16 output points.\u003c\/p\u003e\n\u003cp\u003eQ: What are the current and surge ratings for each channel on this module?\u003c\/p\u003e\n\u003cp\u003eA: Each point supports a maximum continuous load rating of 2 A, with an allowable surge current of up to 10 A for a 10 ms duration.\u003c\/p\u003e\n\u003cp\u003eQ: How are the output channels isolated from each other?\u003c\/p\u003e\n\u003cp\u003eA: The module provides 16 non-commoned outputs with point-to-point electrical isolation rated at 1500 VDC.\u003c\/p\u003e","brand":"Triconex","offers":[{"title":"Default Title","offer_id":67964525609269,"sku":"3604Е","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/4200RXM2_Cocoai_05f4a6d8-2625-4e3e-b9fb-62e25e6ccf96.png?v=1793068394","url":"https:\/\/www.5gplc.com\/products\/triconex-3604e-tricon-digital-output-module","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}