{"product_id":"p0914xb-foxboro-i-a-series-vertical-baseplate","title":"P0914XB Foxboro I\/A Series Vertical Baseplate","description":"\u003cp\u003eThe \u003cstrong\u003eFoxboro P0914XB\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eP0914XB\u003c\/strong\u003e 8-Slot Vertical Baseplate, operates as a dedicated hardware component for fieldbus module power routing and communication bus distribution within Foxboro I\/A Series DCS networks. It accepts dual redundant 24 VDC power feeds to supply up to 8 vertically aligned Fieldbus Modules (FBMs) or Fieldbus Communication Modules (FCMs).\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eP0914XB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eFoxboro\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.48 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e49.2 cm x 19.8 cm x 4.0 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-20 deg C to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eDual-feed redundant 24 VDC bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSlot Capacity\u003c\/td\u003e\n\u003ctd\u003e8 FBM\/FCM module positions\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Orientation\u003c\/td\u003e\n\u003ctd\u003eVertical mounting\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Bus\u003c\/td\u003e\n\u003ctd\u003e2 Mbps Module Fieldbus (HDLC) for 200 Series FBMs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProcess Loop Signal Conditioning and Channel Isolation\u003c\/h3\u003e\n\u003cp\u003eThe Foxboro P0914XB features integrated galvanic isolation across its backplane logic and dual 24 VDC power distribution paths. This physical isolation prevents noise transients and ground loop potentials from propagating along the 2 Mbps HDLC Module Fieldbus lines, safeguarding analog input signals such as 4-20 mA HART loop protocol communications from interference generated in adjacent slots.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Can 200 Series modules be hot-swapped while installed on the P0914XB baseplate?\u003c\/p\u003e\n\u003cp\u003eA: Yes, modules inserted into the 8 baseplate slots support live insertion and removal under system power without disturbing communication traffic on adjacent active slots.\u003c\/p\u003e\n\u003cp\u003eQ: How does the baseplate manage dual power feed redundancy?\u003c\/p\u003e\n\u003cp\u003eA: The board incorporates diode-ORing isolation circuitry across both 24 VDC inputs, allowing seamlessly balanced draw from primary and secondary power supplies without interruption if one source fails.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eMount the baseplate vertically inside the enclosure frame using standard mounting hardware to preserve thermal convection pathways across installed modules. Leave a minimum physical clearance of 50 mm above and below the baseplate for uninhibited heat dissipation.\u003c\/p\u003e\n\u003cp\u003eConnect both 24 VDC redundant power sources using independent, fused branch circuits. All field communication shielding must be tied directly to a single cabinet chassis ground bus using heavy-gauge bonding jumpers. For external cable penetration through the enclosure wall, ensure NPT conduit hubs meet the standard 5-thread engagement criteria to maintain panel environmental protection.\u003c\/p\u003e","brand":"Foxboro","offers":[{"title":"Default Title","offer_id":53394252005685,"sku":"FBM207 P0914XB","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/P0914XB.png?v=1787556230","url":"https:\/\/www.5gplc.com\/products\/p0914xb-foxboro-i-a-series-vertical-baseplate","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}