{"product_id":"mu-taox12-honeywell-8-channel-analog-output-field-termination-assembly-fta","title":"MU-TAOX12 | Honeywell 8-Channel Analog Output Field Termination Assembly (FTA)","description":"\u003ch2\u003e\u003cstrong\u003eTechnical Product Overview\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eMU-TAOX12\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eserves as a specialized 8-point Analog Output Field Termination Assembly (FTA) within the Honeywell TDC 3000 and Experion PKS ecosystems. Engineered for high-precision current loop control, this module converts digital commands into stable 4-20mA signals to drive actuators, valves, and positioners.\u003c\/p\u003e\n\u003cp\u003eA critical engineering advantage of the\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eMU-TAOX12\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eis its elevated field terminal voltage overhead. Compared to standard assemblies like the MU-GAIH13 or MU-GAIH83, this model provides increased drive capability, effectively overcoming higher impedance in extended field wiring runs without compromising signal integrity.\u003c\/p\u003e\n\u003ch2\u003e\u003cstrong\u003eDetailed Engineering Specifications\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eSignal Architecture\u003c\/strong\u003e: 8-Channel isolated current output (typically 4-20mA)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eDigital Resolution\u003c\/strong\u003e: 12-bit D\/A conversion for granular control\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eCalibration Accuracy\u003c\/strong\u003e: ±0.1% of full-scale range at reference conditions\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eInput Power Requirement\u003c\/strong\u003e: Nominal 24 VDC\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eEnvironmental Range\u003c\/strong\u003e: Rated for operation from -40°C to +70°C (-40°F to 158°F)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eDrive Capacity\u003c\/strong\u003e: Enhanced voltage rails to support long-distance cable loops\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eReliability Features\u003c\/strong\u003e: Supports redundant processor configurations for mission-critical loops\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eForm Factor\u003c\/strong\u003e: Approximately 14.5 x 10.5 x 3.5 inches\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003ePhysical Mass\u003c\/strong\u003e: 2.2 lbs (1.0 kg)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eInstallation Standards\u003c\/strong\u003e: Designed for Rittal cabinet mounting using Honeywell-certified hardware\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003e\u003cstrong\u003eInstallation and Hardware Compliance\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cp\u003eTo maintain the thermal and electromagnetic certification of the\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eMU-TAOX12\u003c\/strong\u003e, the assembly must be housed within a standard Rittal enclosure. Integration requires the use of official Honeywell\/Rittal mounting brackets and standoffs. Adhering to these structural requirements ensures the ±0.1% accuracy is maintained even in high-vibration or variable-temperature industrial environments.\u003c\/p\u003e\n\u003ch2\u003e\u003cstrong\u003eFunctional Comparison: MU-TAOX12 vs. MU-GAIH13\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cp\u003eWhile both units handle analog signals, the\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eMU-TAOX12\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eis specifically optimized for output drive. The primary differentiator is the \"Field Terminal Voltage.\" The\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eMU-TAOX12\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eallows for significantly longer wiring distances between the DCS cabinet and the field device, as it can source higher voltage to push the 20mA signal through increased loop resistance.\u003c\/p\u003e\n\u003ch2\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cp\u003e\u003cstrong\u003eDoes the MU-TAOX12 support redundancy?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eYes. The\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eMU-TAOX12\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003ecan be configured in a redundant architecture to ensure that a processor failure does not result in the loss of control over the analog output loops.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eCan this unit be used with non-Honeywell mounting hardware?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eHoneywell documentation strictly specifies standard Rittal mounting hardware to ensure proper grounding and physical support. Using third-party hardware may void the mechanical warranty.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52467065946421,"sku":"MU-TAOX12 51304335-100","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/MU-TAOX1251304335-100.jpg?v=1774237966","url":"https:\/\/www.5gplc.com\/products\/mu-taox12-honeywell-8-channel-analog-output-field-termination-assembly-fta","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}