{"product_id":"is200tturh1cfd-ge-turbine-specific-primary-trip-board","title":"IS200TTURH1CFD GE Turbine Specific Primary Trip Board","description":"\u003cp\u003eConfigured for speed sensing, shaft signal monitoring, and trip circuit execution in Mark VI platforms, the \u003cstrong\u003eGE IS200TTURH1CFD\u003c\/strong\u003e (\u003cstrong\u003eIS200TTURH1C\u003c\/strong\u003e Turbine Specific Primary Trip Board) provides direct physical\/electrical execution. It interfaces directly with the VTUR processor module to handle primary trip circuit switching, passive pulse rate speed inputs, and dedicated breaker coil excitation.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIS200TTURH1CFD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.45 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e12.1 cm x 4.19 cm x 8.26 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-30 to 65 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eBoard Logic Powered via System Interconnect \/ Dedicated 125 VDC Output Channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpeed Sensor MPU Pulse Rate Range\u003c\/td\u003e\n\u003ctd\u003e2 Hz to 20 kHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpeed Sensor Pulse Rate Accuracy\u003c\/td\u003e\n\u003ctd\u003e0.05 percent\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpeed Sensor Input Sensitivity\u003c\/td\u003e\n\u003ctd\u003e27 mV pk\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting \u0026amp; Technology\u003c\/td\u003e\n\u003ctd\u003eSurface mount technology \/ Rack-mounted board assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBoard Compatibility\u003c\/td\u003e\n\u003ctd\u003eCompatible with VTUR module, TTURH1C, and STUR boards (Incompatible with DIN rail-mounted DTUR)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eDeterministic Speed Processing \u0026amp; Circuit Execution\u003c\/h3\u003e\n\u003cp\u003eThe GE IS200TTURH1CFD board interfaces up to twelve passive pulse rate magnetic pickup sensors positioned across turbine toothed wheels, processing pulse rates up to 20 kHz with an accuracy of 0.05 percent. High-density input circuits process induced shaft voltage and shaft current sensor signals to continuously evaluate electrical integrity. Operating across deterministic control networks, the unit provides a dedicated 125 VDC output feed to actuate main generator breaker trip coils for automatic synchronization. Board firmware flash compatibility maintains consistent register mapping with host Mark VI control processors across high-velocity backplane communication channels.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Is the IS200TTURH1CFD terminal board compatible with DIN rail-mounted DTUR module variants?\u003c\/p\u003e\n\u003cp\u003eA: No, the IS200TTURH1CFD is designed for specific rack\/terminal board interconnect structures and is incompatible with DIN rail-mounted DTUR assemblies.\u003c\/p\u003e\n\u003cp\u003eQ: What input sensitivity does the board provide for magnetic pulse rate speed sensors?\u003c\/p\u003e\n\u003cp\u003eA: The passive pulse rate speed sensor input circuits maintain an input sensitivity threshold of 27 mV pk across a sensing range of 2 Hz to 20 kHz.\u003c\/p\u003e\n\u003cp\u003eQ: What is the rating and purpose of the onboard power output channel?\u003c\/p\u003e\n\u003cp\u003eA: The board includes a dedicated 125 VDC output channel engineered to energize the generator main breaker coil during automatic synchronization and emergency trip sequences.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eIsolate all upstream 125 VDC excitation feeds and system power sources before inserting or servicing the IS200TTURH1CFD board.\u003c\/li\u003e\n\u003cli\u003eVerify board compatibility with the connected VTUR processor and ensure nearby DTUR modules are isolated from the signal cable path.\u003c\/li\u003e\n\u003cli\u003eSecure magnetic pickup sensor leads to designated input terminals, using twisted-pair shielded cabling anchored to a single chassis ground point to minimize noise.\u003c\/li\u003e\n\u003cli\u003eRoute 125 VDC breaker coil wiring through isolated conduit pathways away from low-level pulse speed cables to suppress cross-talk.\u003c\/li\u003e\n\u003cli\u003eTorque all mechanical terminal connector screws to standard industrial limits, confirming minimum 5-thread engagement before re-applying system power.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":53412225974581,"sku":"IS200TTURH1CFD","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/IS200TTURH1C_46fb0e33-88db-4872-8b7b-6469d5d55283.png?v=1787820484","url":"https:\/\/www.5gplc.com\/products\/is200tturh1cfd-ge-turbine-specific-primary-trip-board","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}