{"product_id":"honeywell-80363969-100-analog-output-processor-module","title":"Honeywell 80363969-100 Analog Output Processor Module","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell 80363969-100\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003e80363969-100\u003c\/strong\u003e Analog Output Processor Module, operates as a dedicated hardware component for converting digital control signals to analog outputs within Honeywell TDC 3000 and Process Manager architectures. It drives 16 isolated channels outputting 4-20 mA analog current directly to field positioning devices and analog control loops.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e80363969-100\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.0 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e40 mm x 260 mm x 220 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eStandard Backplane Load\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e16 isolated channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Range\u003c\/td\u003e\n\u003ctd\u003e4-20 mA analog current\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible Terminal Boards\u003c\/td\u003e\n\u003ctd\u003eMU-TAOY22, MU-TAOY52, MC-TAOY22, MC-TAOY52\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eChannel-to-Channel Isolation and Loop Protocol Response\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell 80363969-100\u003c\/strong\u003e incorporates internal optical decoupling across all 16 current loops to maintain channel-to-channel isolation. This galvanic barrier protects internal microprocessor logic against field ground loops and high-voltage electrical surges. When operating with 4-20 mA HART loop protocol field positioners, the digital-to-analog converter stage provides continuous loop impedance management to stabilize signal conversion over extended cable distances.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Are terminal connections made directly to the front face of the 80363969-100 module?\u003c\/p\u003e\n\u003cp\u003eA: No. Field cabling connects to compatible external terminal assemblies such as the MU-TAOY22, MU-TAOY52, MC-TAOY22, or MC-TAOY52, which link to the module via dedicated multi-conductor cables.\u003c\/p\u003e\n\u003cp\u003eQ: Can an individual 4-20 mA output channel be configured as a voltage output?\u003c\/p\u003e\n\u003cp\u003eA: No. The internal digital-to-analog conversion circuitry is designed strictly for 4-20 mA current loop driving and does not provide native voltage output options.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eTurn off main rack power and field loop power supplies prior to seating or removing the module from the chassis slot.\u003c\/li\u003e\n\u003cli\u003eAlign the module circuit board with the chassis card guides and push firmly until the rear connectors seat securely into the backplane.\u003c\/li\u003e\n\u003cli\u003eFasten the module retaining screws to ensure proper chassis grounding and mechanical retention under operational vibration.\u003c\/li\u003e\n\u003cli\u003eRoute field signal cables through grounded, shielded conduits and separate them from high-voltage AC power wiring to prevent noise coupling.\u003c\/li\u003e\n\u003cli\u003eVerify that shield drain wires are tied to a single-point system ground block at the cabinet cable entrance.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":53191830372661,"sku":"80363969-100","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/80363969-100.png?v=1784620392","url":"https:\/\/www.5gplc.com\/products\/honeywell-80363969-100-analog-output-processor-module","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}