{"product_id":"ge-is200trtdh1c-rtd-input-terminal-board","title":"GE IS200TRTDH1C RTD Input Terminal Board","description":"\u003cp\u003eThe \u003cstrong\u003eGE IS200TRTDH1C\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eIS200TRTDH1C\u003c\/strong\u003e RTD Input Terminal Board, operates as a dedicated hardware component for multi-channel temperature signal acquisition within Mark VIe distributed control platforms.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIS200TRTDH1C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e6.25 in x 4.25 in\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e400 W (Total capacity)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Capacity\u003c\/td\u003e\n\u003ctd\u003e16 three-wire RTD inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProfinet \/ EtherNet\/IP Deterministic Networks\u003c\/h3\u003e\n\u003cp\u003eThe IS200TRTDH1C manages the termination and conditioning of 16 three-wire RTD signals. The board utilizes integrated noise-reduction circuitry at each input to mitigate high-frequency interference and surge events before signal conversion. The terminal board interfaces with I\/O processors (VRTD boards) via two DC-type connectors to digitize temperature values for controller transmission. Deterministic operation is maintained through synchronized communication between the TRTD and the I\/O processors, ensuring that thermal data is ingested within established controller scan cycles. I\/O density scaling is supported through the board's modular architecture, allowing for straightforward expansion of temperature monitoring points within the Mark VIe control cabinet.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Can the IS200TRTDH1C be used in TMR (Triple Modular Redundant) systems?\u003c\/p\u003e\n\u003cp\u003eA: No. The IS200TRTDH1C is a simplex configuration board. For TMR applications, the TRTDH1B variant is required, which provides the necessary six DC-type connectors to interface with three redundant VRTD boards.\u003c\/p\u003e\n\u003cp\u003eQ: How does the board handle high-frequency noise on RTD inputs?\u003c\/p\u003e\n\u003cp\u003eA: The board features dedicated surge and noise-reduction circuitry at the point of input. This circuitry filters induced noise from field cabling before the signal is passed to the analog-to-digital conversion stage.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal Block Wiring\u003c\/strong\u003e: Use the two provided barrier-type terminal blocks for all field connections. Ensure that the three-wire RTD leads are terminated securely to prevent resistance imbalances, which can cause significant measurement errors in temperature readings.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting\u003c\/strong\u003e: Secure the board onto a flat panel or DIN-rail. Ensure a clean mechanical connection to the cabinet ground to maximize the effectiveness of the noise suppression circuitry.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSignal Segregation\u003c\/strong\u003e: Maintain physical separation between RTD input wiring and high-current power or AC control wiring to minimize inductive noise ingress.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnector Seating\u003c\/strong\u003e: Ensure the two DC-type connectors linked to the VRTD boards are fully seated and locked. Loose connections can introduce contact resistance that degrades the precision of the temperature feedback loop.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":52949516812597,"sku":"IS200TRTDH1C","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/IS200TRTDH1C1.png?v=1780307489","url":"https:\/\/www.5gplc.com\/products\/ge-is200trtdh1c-rtd-input-terminal-board","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}