{"product_id":"emerson-con041-cn-pr6423-000-031-proximity-sensors","title":"Emerson CON041-CN+PR6423\/000-031 Proximity Sensors","description":"\u003cp\u003eThe \u003cstrong\u003eEmerson CON041-CN+PR6423\/000-031\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eCON041-CN \/ PR6423\u003c\/strong\u003e Proximity Sensors, operates as a dedicated hardware component for non-contact shaft vibration, position, and eccentricity measurement within Emerson MMS 6000 and MMS 3000 platforms. The hardware system links an 8 mm inductive proximity probe with the CON041-CN signal converter module to evaluate spatial displacement against conductive ferromagnetic targets. High-frequency oscillator fields convert dynamic surface gap deviations directly into linear continuous voltage or current signals without physical mechanical wear.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCON041-CN+PR6423\/000-031\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eEmerson\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-35 to +180 deg C (Sensor) \/ -35 to +150 deg C (Cable)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eStandard loop power (24 VDC supply)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupply Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasurement Range\u003c\/td\u003e\n\u003ctd\u003eTypically +\/-2 mm peak-to-peak; linear up to 4 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensitivity\u003c\/td\u003e\n\u003ctd\u003e8 V\/mm (203.2 mV\/mil) +\/-5%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFrequency Range\u003c\/td\u003e\n\u003ctd\u003e0 to 20000 Hz (-3 dB)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Signal\u003c\/td\u003e\n\u003ctd\u003eAnalog voltage (0-10 V) or current (4-20 mA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTarget Material\u003c\/td\u003e\n\u003ctd\u003eFerromagnetic steel (e.g., 42CrMo4)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIngress Protection\u003c\/td\u003e\n\u003ctd\u003eIP65\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e4-20 mA HART Loop Protocol \u0026amp; Channel Isolation\u003c\/h3\u003e\n\u003cp\u003eThe CON041-CN signal converter incorporates high-speed conditioning circuitry with a \u0026lt; 15 us rise time to support broad dynamic frequency ranges up to 20000 Hz. The signal path provides continuous channel-to-channel isolation to prevent potential differences between adjacent sensor loops from introducing noise into process monitoring circuits. Configured for standardized 4-20 mA HART loop protocol signaling alongside direct voltage modes, the driver compensates for thermal variations across the -35 to +180 deg C range to maintain exact scale factor linearity.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How is the CON041-CN converter secured in control cabinets?\u003c\/p\u003e\n\u003cp\u003eA: The converter module utilizes a standardized DIN rail mounting chassis for direct snap-on installation within industrial control enclosure racks.\u003c\/p\u003e\n\u003cp\u003eQ: What target surface material is required for the PR6423 sensor calibration?\u003c\/p\u003e\n\u003cp\u003eA: The sensor sensitivity of 8 V\/mm is factory-calibrated for ferromagnetic steel targets, such as 42CrMo4 steel shafts.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eMaintain an unobstructed lateral clearance zone around the 8 mm probe tip equal to at least 1.5 times the tip diameter to eliminate uncalibrated side-wall interference from metallic surroundings. Mount the CON041-CN converter securely onto a standard DIN rail inside a protective enclosure. Route sensor extension leads through dedicated grounded metallic conduit, keeping signal paths physically separated from high-voltage AC feeds or motor drive connections. Connect all cable shields to technical functional earth at a single point only to prevent circulating ground currents.\u003c\/p\u003e","brand":"EMERSON","offers":[{"title":"Default Title","offer_id":53346978332981,"sku":"CON041-CN+PR6423\/000-031","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/CON021913-040_PR6423015-000-CN_efb792eb-7c18-4092-b7d8-a0bfc1d43566.jpg?v=1787197962","url":"https:\/\/www.5gplc.com\/products\/emerson-con041-cn-pr6423-000-031-proximity-sensors","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}