{"product_id":"5x00357g01-digital-i-o-module-westinghouse-ovation","title":"5X00357G01 Digital I\/O Module | Westinghouse Ovation","description":"\u003cp\u003eConfigured for high-speed event capture in Ovation control networks, the \u003cstrong\u003eWestinghouse Ovation 5X00357G01\u003c\/strong\u003e (\u003cstrong\u003e5X00357G01\u003c\/strong\u003e) Digital I\/O Module provides direct physical electrical execution for monitoring 16 differential input channels. The module processes 24 VDC inputs from field devices including switches, alarms, and discrete sensors, utilizing programmable event filters to mitigate signal noise.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e5X00357G01\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eWestinghouse\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.35 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e150 mm x 20 mm x 190 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to 70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 10 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003e16 Differential Channels (24 VDC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eChannel-to-Channel Isolation\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003e5X00357G01\u003c\/strong\u003e employs galvanic channel-to-channel isolation to maintain signal integrity and prevent common-mode noise propagation between discrete input loops. This isolation architecture is necessary to preserve the accuracy of event timestamps and prevents electrical ground potential differences from affecting the logic state detection across the 16 channels. Each channel includes hardware-level break detection to monitor loop continuity, ensuring that field-side open or short circuit conditions are identified and reported to the controller without impacting adjacent channel operations.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: Does this module support redundant configuration for high-availability applications?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the 5X00357G01 supports configuration in redundant pairs. In such setups, the secondary module remains in a synchronized state to ensure seamless transition if the primary module experiences a hardware fault.\u003c\/p\u003e\n\u003cp\u003eQ: How do the programmable event filters function?\u003c\/p\u003e\n\u003cp\u003eA: The event filters are configurable via the Ovation controller software; they allow for the definition of debounce times to suppress high-frequency noise or contact bounce, ensuring that only valid, stable state changes are recorded as events.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eEnsure the I\/O chassis is de-energized before inserting the module into the backplane to prevent contact arcing.\u003c\/li\u003e\n\u003cli\u003eAlign the module with the chassis guide rails and push firmly until the locking lever fully engages the connector.\u003c\/li\u003e\n\u003cli\u003eTerminate 24 VDC field wiring at the I\/O terminal block, ensuring that twisted-pair cabling is used for all differential signal paths to minimize electromagnetic interference.\u003c\/li\u003e\n\u003cli\u003eConnect the cable shield drain wire to the cabinet ground bus at a single common point to prevent the formation of ground loops.\u003c\/li\u003e\n\u003cli\u003eVerify per-channel LED indicators during system commissioning to confirm that field status transitions are accurately reflected in the control software.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"EMERSON","offers":[{"title":"Default Title","offer_id":52955305345333,"sku":"5X00357G01","price":66.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0973\/7630\/5461\/files\/5X00226G02_5db461f4-c714-4073-9b39-bc98fa02d2bf.png?v=1780453282","url":"https:\/\/www.5gplc.com\/products\/5x00357g01-digital-i-o-module-westinghouse-ovation","provider":"High Five PLC Solution Limited","version":"1.0","type":"link"}